1. 시동전 확인사항

 . CRANK CHAMBER GOVERNOR 용 윤활유 LEVEL 확인

 나. 실린더JACKET PREHEATER 작동상태 확인(40~50)

 . 연료유 계통 및 밸브 확인

 . 밧데리 충전상태확인( DC 24V ~ 30 V )

 . RADIATOR FAN DOOR OPEN 확인

 

2. 시동 방법

 . Starting by the batteries.

      1) The Change-Over Switch is switch ‘AUTO” position over ‘MANU’ position.

      2) Check opened the F.O. Shut Solenoid Valve for Governor. (Normally ‘OPEN’ condition)

      3) Push the Start Button.

 

 나. Starting by the Hydraulic Motor.

      1) The Change-Over Switch is switch ‘AUTO” position over ‘MANU’ position.

      2) Close the F.O. Shut Solenoid Valve for Governor.

      3) Raise the hydraulic pressure until 1300 PSI by pumping the hand Hyd. Pump in order to starting.

      4) Push the Hyd. Starting Valve after lease the Lock Pin.

 

 다. Starting by the Instrumental Panel

      1) The Change-Over Switch is switch ‘AUTO” position over ‘MANU’ position.

      2) Handle the Manual Switch in Instrumental Panel of EM’CY GEN’ at once.

      3) Check that L.O. PRESS’ (3.5 ~ 5.3 BAR), L.O TEMP’ (82 ~107 ℃), C.F.W PRESS’ (MAX. 2.8 BAR),

         C.F.W TEMP’ (71 ~ 93 ℃), ENGINE RPM (1800 RPM)

 

3. 정지

 . 비상배전반의 ACB OPEN

 . GOVERNOR F.O SHUT SOLENOID VALVE OPEN상태인지 확인한다.

 . 발전기 CONTROL PANEL 상에서 STOP BUTTON을 누른다.

 . 비상시 작동이 가능하도록 발전기 CONTROL PANEL 상의 SELECTOR SWITCH를 AUTO. 상태로 전환한다.

 

4. 관리 및 정비

 가. 비상발전기는 기관실의 주발전기가 비상전원을 공급하지 못하였을 때 45초안에

     자동 급전되어야 하는 중요 기기이므로 선박안전점검 CHECK LIST에 의거 철저한

     점검을 실시한다.

 . 자동기동방식의 비상발전기용 BATTERY는 최소한 3회의 연속시동이 가능하도록 BATTERY 상태

      ( 전체 전압 24~30V )를 주기적으로 확인한다.

 다. 연료유는 비상조명 및 비상작동 설비의 최소 18시간 운전에 필요한 충분한 양

      ( 1152 LTR :1800 RPM에서 100%의 부하로 18시간 운전가능한 연료량 )을 보유하여야 한다.